Title 24 Cool Roof Requirements for Orange County Re-Roofs

California's Energy Code sets reflectance rules for re-roofs, and in Orange County the answer depends on two things: which climate zone your ZIP code is in, and whether your roof is steep or low-slope. Here is how the current rules work, where the exceptions are, and what they mean for tile, shingle and flat roofs.

What Title 24 Part 6 is, and which version applies

Title 24, Part 6 of the California Code of Regulations is the state's Building Energy Efficiency Standards, usually just called the Energy Code. It is updated on a three-year cycle by the California Energy Commission. The 2025 Energy Code applies to buildings whose permit applications are submitted on or after January 1, 2026. Projects that applied for permits before that date fall under the 2022 code.

For single-family re-roofs, the cool-roof values in the 2025 code are the same ones that applied under the 2022 code, so most homeowners will not notice a difference between cycles. The section that governs re-roofs on existing single-family homes is Section 150.2(b)1I, which covers roofing products and insulation when the exterior surface of an existing roof is replaced. The Energy Commission has also published a restructured, renumbered version of the 2025 code for information only; the formally adopted section numbers are the ones your building department will use.

Nothing in this guide replaces the code itself or your city's interpretation of it. The building department that issues your re-roof permit has the final word, and some cities adopt local amendments.

When a re-roof triggers the rules

The re-roof requirements apply to replacements of the exterior surface of an existing roof, including adding a new surface layer on top of an existing one, where more than 50 percent of the roof is being replaced. Some city compliance forms phrase it as 50 percent or more, so treat a project right at half the roof as one to confirm with the building department.

In practice, that means a full tear-off and replacement, an overlay, or a re-coat of most of a roof can all trigger the requirements. A repair that replaces a small section, such as one valley or one slope on a large roof, generally does not. When a roof has more than one pitch, the requirements are typically based on the pitch that makes up the majority of the roof.

The code splits roofs by slope. A low-sloped roof has a rise of less than 2 inches per 12 inches of run. A steep-sloped roof has a rise of 2 in 12 or more. Nearly all tile and shingle roofs in Orange County are steep-sloped. Flat roofs, roof decks, many patio covers and the flat sections of mid-century and Spanish Revival homes are low-sloped.

Orange County's climate zones: 6 and 8

California is divided into 16 building climate zones, and the Energy Commission assigns them by ZIP code. Based on the Commission's ZIP code list, Orange County falls into two zones: Climate Zone 6 along the coast and much of the south county, and Climate Zone 8 for most inland cities. The difference matters a great deal for sloped roofs.

Examples of ZIP codes the Commission lists in Climate Zone 6 include Huntington Beach, Newport Beach, Costa Mesa, Laguna Beach, Laguna Niguel, Laguna Hills, Aliso Viejo, Dana Point, San Juan Capistrano, San Clemente, Seal Beach, Westminster and Fountain Valley. Examples in Climate Zone 8 include Anaheim, Santa Ana, Orange, Tustin, Fullerton, Brea, Yorba Linda, most of Garden Grove, Cypress, Buena Park, Irvine, Lake Forest, Mission Viejo, Rancho Santa Margarita, Ladera Ranch and Trabuco Canyon.

Treat that list as a starting point, not a ruling. Climate zones follow ZIP code assignments rather than city limits, some cities straddle two zones, and where a ZIP code spans more than one zone the local jurisdiction may designate a single zone for it. The Energy Commission's online climate zone lookup and your building department will confirm the zone for a specific address.

Steep-slope roofs: required in Zone 8, not in Zone 6

For steep-sloped roofs, the cool-roof requirement applies in Climate Zones 4 and 8 through 15. In Orange County, that means inland Zone 8 homes are covered and coastal Zone 6 homes are not. A tile or shingle re-roof in Dana Point or Huntington Beach does not have to meet a reflectance target; the same re-roof in Anaheim or Mission Viejo does, unless an exception applies.

Where it applies, new roofing products on a steep-sloped roof must have a minimum aged solar reflectance of 0.20 and a minimum thermal emittance of 0.75, or a minimum Solar Reflectance Index (SRI) of 16. Aged means the value after three years of weathering, as rated through the Cool Roof Rating Council. A 0.20 aged reflectance is a modest bar. Many light and mid-tone concrete tiles and a growing number of shingle colors meet it, including some that do not look white at all. Very dark colors are the ones that usually fall short.

  • Ceiling insulation of at least R-38, or a ceiling assembly U-factor of 0.025 or lower, is treated as equivalent compliance
  • A qualifying radiant barrier in the attic, not installed directly over spaced sheathing, is treated as equivalent
  • R-2 or greater continuous insulation above or below the roof deck is treated as equivalent
  • Roof area covered by building-integrated photovoltaic or solar thermal panels is exempt from the reflectance values
  • Roof constructions weighing at least 25 pounds per square foot are exempt; standard concrete tile generally weighs well under that
  • An equivalence for having no ducts in the attic exists only in Climate Zones 2, 4, 9, 10, 12 and 14, so it does not help Zone 8 homes in Orange County

Low-slope roofs: required in both Orange County zones

Flat and low-slope roofs face a stricter target and a wider map. New roofing products on low-sloped roofs in Climate Zones 4 and 6 through 15 must have an aged solar reflectance of at least 0.63 and a thermal emittance of at least 0.75, or a minimum SRI of 75. Because Zone 6 is included, this applies across all of Orange County, coast and inland alike. In practice, a compliant low-slope roof is usually a white or very light membrane or coating.

There is a trade-off for owners who do not want a highly reflective surface. Adding continuous insulation at the roof deck lowers the required aged reflectance. In Climate Zones 6 and 7, R-2 lowers it to 0.60, R-4 to 0.55, R-6 to 0.50, R-8 to 0.45, and R-10 removes the reflectance requirement entirely. In Climate Zone 8 the same steps require R-16, R-18, R-20, R-22 and R-24. Area covered by building-integrated solar and roofs weighing 25 pounds per square foot or more are exempt, as with steep roofs.

Low-slope re-roofs also carry an insulation requirement that depends on zone. In Zones 6 and 7 there is no added insulation requirement for a low-slope roof alteration. In Zone 8, the replaced roof is generally expected to reach R-14 continuous insulation or an assembly U-factor of 0.039. There are exceptions, including existing roofs that already have R-10 continuous insulation, roofs insulated with at least R-19 between the rafters in contact with the deck, and reduced insulation where added thickness would push base flashings at walls, doors or rooftop equipment below the heights manufacturers and the Residential Code require.

Product ratings and paperwork

To count toward compliance, a roofing product's thermal emittance and three-year aged solar reflectance must be certified and labeled under the Cool Roof Rating Council program, as Title 24 Part 1 requires. Products are listed in the Council's Rated Product Directory by manufacturer, product type and color. A product that is not certified must use default values, which for asphalt shingles is an aged reflectance of 0.08 and for other roofing products 0.10, with an emittance of 0.75. Those defaults fail the steep-slope target, so an unrated product effectively does not comply.

On a permitted re-roof, the compliance path is documented on the state's residential alteration forms. The certificate of compliance for a prescriptive re-roof is typically the CF1R-ALT-01-E, and where a cool roof is installed the contractor completes an installation certificate, the CF2R-ENV-04-E. Liquid-applied coatings used to meet cool-roof requirements must cover the entire roof surface at the manufacturer's recommended thickness or coverage.

What this means for common Orange County roofs

Coastal tile or shingle re-roof (Zone 6): no reflectance requirement for the sloped roof. You can choose color freely, subject to your HOA, fire-zone rules and any city design guidelines. Any flat sections being replaced as part of a re-roof of more than half the roof still need to meet the low-slope rule or the insulation trade-off.

Inland tile or shingle re-roof (Zone 8): either choose a rated product that meets 0.20 aged reflectance, or document an equivalent such as R-38 attic insulation or a qualifying radiant barrier. Many homes built or upgraded in recent decades already have one of those, and adding attic insulation during a re-roof is a common way to keep a darker color.

Flat roof or roof deck anywhere in Orange County: plan on a white or light reflective membrane, or on adding enough deck insulation to use the trade-off table. In Zone 8, also plan for the low-slope insulation requirement unless an exception applies.

Tile reset on new underlayment: how a lift-and-relay of existing tile is treated under the reflectance rule can depend on the building department's reading of what counts as new roofing product. In Zone 6 it is a non-issue for steep roofs. In Zone 8, confirm with the city during permitting; the attic insulation and radiant barrier equivalents often resolve it either way.

Cool roof rules are separate from fire rules

Title 24 Part 6 is about energy. Fire requirements come from other parts of the building code. If your home is in a mapped fire hazard severity zone, the re-roof will generally need a Class A roof assembly regardless of climate zone, and the state's 2025 fire hazard map update changed the boundaries in many Orange County cities. Concrete and clay tile, most asphalt shingles and metal can be installed as Class A assemblies; wood shake generally cannot. The two sets of rules stack: an inland hillside home may need both a Class A assembly and a cool-rated or equivalent roof.

FAQ

Questions homeowners ask

Does my Orange County re-roof need a cool roof?

For a sloped tile or shingle roof, only if you are in Climate Zone 8, which covers most inland cities, and even then exceptions such as R-38 attic insulation or a radiant barrier can satisfy the rule. For a flat or low-slope roof, the reflectance rule applies in both Zone 6 and Zone 8 when more than half the roof is replaced, with an insulation trade-off available.

Does a cool roof have to be white?

Not for steep roofs. The steep-slope target is an aged solar reflectance of 0.20 or an SRI of 16, which many tan, gray, terracotta and even some darker cool-pigment products meet. Low-slope roofs have a much higher target that usually means white or very light, unless you add deck insulation under the trade-off table.

Does a roof repair trigger Title 24?

Generally not. The re-roof requirements apply when more than 50 percent of the roof surface is replaced. Replacing a damaged section or a single slope on a larger roof is usually treated as a repair, but confirm with your building department if you are close to half the roof.

How do I find my building climate zone?

Use the California Energy Commission's climate zone lookup by address or ZIP code, or ask your city's building department. Orange County ZIP codes fall in Zone 6 or Zone 8, but some cities have ZIP codes in both, and the city's designation controls.